Menu
Dresser
Dresser
Dresser
Dresser
Dresser
Dresser
Dresser
Dresser
Dresser
Dresser
Dresser
Dresser
Quick-Cam repair clamps, emergency kits, Ultra-Sleeve bell joint repair and abandoned corporation stop fittings.

This collection covers Dresser repair products for leaks and breaks on live water mains: Quick-Cam Extended and Regular Range repair clamps, emergency repair kits and panels, Ultra-Sleeve bell joint repair sleeves and abandoned corporation stop fittings. It serves utility crews and contractors who need the main back in service fast.
We supply every Quick-Cam width, lug and outlet build by Dresser part number. Call 1-888.510.4036 or email sales@watermainsupply.com. Genuine Dresser equipment, factory-new in original packaging — sold and supported by Watermain Supply, an independent industrial supplier.
Quick-Cam Extended Range: up to 200 PSI on water and 125 PSI on gas. Ultra-Sleeve: up to 200 PSI. Abandoned corp stop fitting: up to 250 PSI. Emergency kits: 150 PSI. Regular Range: rating on the product label; we confirm it before you order.
One Extended Range clamp covers up to 0.9 in of pipe OD, so fewer sizes cover more pipe.
Works on ductile iron, cast iron, steel, PVC and asbestos cement mains. Measure OD with a pi tape.
Send the pipe OD, pipe material and line content. We confirm the part number before you order. 1-888.510.4036 · sales@watermainsupply.com
Pick by the damage: a hole or break, a leaking bell joint, or an old corporation stop.

All Stainless
Cam lug repair clamp with waffled mat gasket and O-ring seal beads. Stainless or ductile lugs, with or without outlet.

Ductile Iron
Encloses a leaking bell, coupling or AC collar without shutting the main down.

304 Stainless
Covers an old corporation stop with a full gasket and stainless cap when a lead service is retired.
| Listing | Range | Rating (Dresser) | Build | Use |
|---|---|---|---|---|
| Quick-Cam EX, All Stainless | 2 to 54 in | 200 PSI water | Stainless lugs | Repair |
| Quick-Cam EX, Stainless, Outlet | 4 to 12 in | 200 PSI water | NPT or CC outlet | Repair plus tap |
| Quick-Cam EX, Ductile | 3 to 54 in | 200 PSI water | Ductile lugs | Repair |
| Quick-Cam RR, All Stainless | 2 to 12 in | Per label | Stainless lugs | Repair |
| Emergency Kit | 2 to 54 in | 150 PSI water | Panels | Truck stock |
| Ultra-Sleeve | 2 to 36 in | 200 PSI | Ductile iron | Bell joints |
| Abandoned Corp Stop | 4 to 16 in | 250 PSI | 304 stainless | Corp stops |
| Need | Dresser | Smith-Blair (also on our site) | Verdict |
|---|---|---|---|
| Full circle repair clamp | Quick-Cam: up to 0.9 in OD per clamp, 2 to 54 in | Style 226: stainless, 2.35 to 14.4 in OD | Quick-Cam covers wider OD per clamp and larger mains; Smith-Blair 226 is a proven bolt-up design many crews already stock |
| Bell joint repair | Ultra-Sleeve: two-piece encapsulation | Style 274: bell joint leak clamp, 2 to 36 in | Ultra-Sleeve encloses the whole joint with no gland; Smith-Blair 274 is the simpler clamp for a leaking bell |
Both brands are on our site. Tell us the pipe OD and the damage and we recommend the better fit.
| Damage | Pipe | Recommended | Notes |
|---|---|---|---|
| Hole, crack or break | 2 to 12 in | Quick-Cam Extended Range | Pick width to cover the damage |
| Break needing a service tap | 4 to 12 in | Quick-Cam with outlet | NPT or CC |
| Large main break | 14 to 54 in | Quick-Cam multi-panel | Ductile or stainless lugs |
| Truck stock for emergencies | 2 to 54 in | Emergency kit | 15 or 24 in wide |
| Leaking bell or coupling | 2 to 36 in | Ultra-Sleeve | Measure over the bell |
| Old corporation stop | 4 to 16 in | Abandoned corp stop fitting | 3 or 4 in outlet |
Use a pi tape on the pipe barrel. Every Quick-Cam option is an OD range; pick the range your reading falls in.
Choose a clamp at least a few inches wider than the damaged section so the gasket seals on sound pipe.
Repair clamps seal; they do not restrain. Anchor the pipe where pullout could occur. Do not reuse a clamp until it is refurbished at the factory.
Extended range cam lugs with a built-in handle.
Multi O-ring seal beads on an NSF-61 NBR gasket.
Install in tight spaces.
NPT or CC tapped outlets from 1/2 to 2 in.
Ultra-Sleeve installs on a live main.
Every variant ends with the Dresser part number.




Genuine Dresser parts, listed by Dresser part number.
We check pipe OD, material and line content against Dresser data before we quote.
We carry Dresser and Smith-Blair. If one is not the right fit for your job, we say so.
Every variant ends with the Dresser part number, so you get exactly what the spec calls for.
Net terms for contractors, utilities and municipalities on approved accounts.
Dresser technical specifications and installation instructions are attached to each product.
Houston-based team for the Gulf Coast and nationwide shipping.
12 months from the date of purchase under Dresser published warranty terms.
Extended Range clamps are rated up to 200 PSI on water and 125 PSI on gas. Regular Range ratings are on the product label; we confirm before you order.
Extended Range covers up to 0.9 in of OD per clamp. Regular Range covers a narrower band per size.
Not until it is refurbished at the factory with new bolts and gaskets.
Leaking bells, couplings with two or more bolts, and AC collars, without shutting the main down.
Quick-Cam: 180°F continuous with the standard NBR gasket.
Use a pi tape on the pipe OD. For the Ultra-Sleeve, measure over the bell or coupling.
Yes. Email sales@watermainsupply.com with the part numbers.
Send the pipe OD, material and line content. We confirm the Dresser part number and quote the same day.