TIGERFLOW Tigercub simplex variable speed booster system

TIGERFLOW Booster Pumps

TIGERFLOW variable speed booster pumps and packaged booster systems, built in Dallas, Texas.
The self-priming Ocelot 25 (120V) and Ocelot 60 have the drive, expansion tank and check valves built in; the Ocelot Duplex runs two Ocelot 60s lead-lag to 144 GPM.
Tigercub simplex systems pair a CD vertical multistage pump with a VFD and UL 508A disconnect panel as one UL / cUL listed package: 22 to 154 GPM and up to 305 psi of boost.
Single phase from 120V, three phase to 460V, 1 to 7-1/2 HP.
Every booster carries TIGERFLOW's 12-month warranty; tanks, purge valves, seals and motors are listed separately.
We check your duty point against TIGERFLOW's published performance before it ships. Call 1-888.510.4036.

8 products
Sort by:
Price, low to high
Sort by:
Price, low to high
TIGERFLOW Ocelot 25 Variable Speed Booster Pump, 70 PSI Max Boost - 24 GPM Max / 1 HP - 120V 1Ph / Ocelot 25
TIGERFLOW Ocelot 25 variable speed simplex booster pump, angled view

TIGERFLOW

Free Shipping $499 or more

TIGERFLOW Ocelot 25 Variable Speed Booster Pump, 70 PSI Max Boost - 24 GPM Max / 1 HP - 120V 1Ph / Ocelot 25

Price
$980.49
TIGERFLOW Ocelot 60 Variable Speed Booster Pump
TIGERFLOW Ocelot 60 variable speed simplex booster pump, angled view

TIGERFLOW

Free Shipping $499 or more

TIGERFLOW Ocelot 60 Variable Speed Booster Pump

Price
$2,087.61
TIGERFLOW Tigercub CD5 Simplex Variable Speed Booster System
TIGERFLOW Tigercub CD5 simplex variable speed booster system with VFD and disconnect

TIGERFLOW

Free Shipping $499 or more

TIGERFLOW Tigercub CD5 Simplex Variable Speed Booster System

Price
From $7,679.92
TIGERFLOW Tigercub CD3 Simplex Variable Speed Booster System
TIGERFLOW Tigercub CD3 simplex variable speed booster system with VFD and disconnect

TIGERFLOW

Free Shipping $499 or more

TIGERFLOW Tigercub CD3 Simplex Variable Speed Booster System

Price
From $7,941.31
TIGERFLOW Tigercub CD10 Simplex Variable Speed Booster System
TIGERFLOW Tigercub CD10 simplex variable speed booster system with VFD and disconnect

TIGERFLOW

Free Shipping $499 or more

TIGERFLOW Tigercub CD10 Simplex Variable Speed Booster System

Price
From $8,627.87
TIGERFLOW Ocelot Duplex Variable Speed Booster System - Lead-Lag
TIGERFLOW Ocelot duplex booster skid, two pumps with stainless manifolds

TIGERFLOW

Free Shipping $499 or more

TIGERFLOW Ocelot Duplex Variable Speed Booster System - Lead-Lag

Price
$8,798.06
TIGERFLOW Tigercub CD15 Simplex Variable Speed Booster System
TIGERFLOW Tigercub CD15 simplex variable speed booster system with VFD and disconnect

TIGERFLOW

Free Shipping $499 or more

TIGERFLOW Tigercub CD15 Simplex Variable Speed Booster System

Price
From $10,242.02
TIGERFLOW Tigercub CD20 Simplex Variable Speed Booster System
TIGERFLOW Tigercub CD20 simplex variable speed booster system with VFD and disconnect

TIGERFLOW

Free Shipping $499 or more

TIGERFLOW Tigercub CD20 Simplex Variable Speed Booster System

Price
From $11,021.47

TIGERFLOW Booster Pumps

TIGERFLOW Systems · Dallas, Texas

TIGERFLOW
Booster Pumps & Systems

Variable speed constant pressure boosters from a Texas pump builder: the self-priming Ocelot 25 and Ocelot 60 for homes and light commercial work, the lead-lag Ocelot Duplex, and the Tigercub simplex systems, a CD vertical multistage pump, drive and UL 508A disconnect panel factory tested as one UL / cUL listed package. Up to 305 psi of boost and 154 GPM, with engineering-led sizing from Watermain Supply.

TIGERFLOW Tigercub simplex variable speed booster system with VFD and disconnect panel
24-154 GPMMax flow by model
305 psiMax boost, Tigercub CD5-20
1 to 7-1/2 HP120V to 460V
Self-PrimingOcelot, 9 ft standard
UL / cULListed Tigercub package

TIGERFLOW Systems is a Dallas, Texas manufacturer that has designed and built pumping equipment for more than 35 years: domestic water boosters, HVAC pumping systems and engineered pump packages for hospitals, schools, hotels, high rises and municipal water. Its booster range starts with the Ocelot, a compact permanent magnet pump with its own drive, and steps up to the Tigercub, a packaged simplex system built around the TIGERFLOW CD vertical multistage pump.

Watermain Supply supplies the full Ocelot and Tigercub range, plus the expansion tanks, thermal purge valves, seals, pump ends and motors that keep them running. Send us your flow, floors and incoming pressure and we check the duty against TIGERFLOW’s published performance before you order. Call 1-888.510.4036. Genuine TIGERFLOW equipment, factory-new in original packaging — sold and supported by Watermain Supply, an independent industrial supplier.

Will a TIGERFLOW Booster Work for You?

The four questions buyers ask first, answered from TIGERFLOW’s published data.

12-Month Warranty

Every Ocelot and Tigercub is covered for 12 months from the date of purchase under TIGERFLOW’s published warranty terms. Seals, pump ends, motors and tanks are listed separately, so a Tigercub can be rebuilt part by part.

Built to Last

Stainless steel pumps throughout: AISI 304 bodies on the Ocelot, 304/316 stainless impellers on the Tigercub CD pump. Low-flow detection slows or stops the Ocelot when demand drops; Tigercub adds a low suction alarm, a non-slam check valve and vibration isolators as standard.

The Fit Limits

Ocelot: 24 to 77 GPM per pump, 144 GPM as a duplex, up to 99 psi of boost, self-priming. Tigercub: 22 to 154 GPM, up to 305 psi, flooded or pressurized suction, 1 to 7-1/2 HP on 208-230V single phase or 208-230V and 460V three phase.

Size It Now

Enter flow, floors and inlet pressure and the calculator returns the TIGERFLOW models, and the other brands we carry, that hold your setpoint.

Run the Calculator

Or send the numbers: sales@watermainsupply.com · 1-888.510.4036

TIGERFLOW Booster Models

Three ways to boost: one self-contained Ocelot, two Ocelots on a skid, or a packaged Tigercub system. Pick by flow, pressure and whether the building needs a standby pump.

TIGERFLOW Ocelot 60 variable speed simplex booster pump

Ocelot 25 and Ocelot 60

Self-priming, drive on board

24 / 77 GPMMax flow
70 / 99 psiMax boost
1 / 2 HPPermanent magnet
IPX6Outdoor-rated cover

A stainless pump, permanent magnet motor and variable speed drive in one compact unit, with a built-in expansion tank and check valves on suction and discharge. Set the pressure on the keypad and the drive holds it, slowing or stopping as demand falls.

  • Ocelot 25: 39 psi at 13 GPM rated, 120V, 1 in NPT
  • Ocelot 60: 61 psi at 35 GPM rated, 208-230V 1Ph or 3Ph, 2 in NPT
  • Self-priming to 9 ft, up to 25 ft by installation
  • Water to 167°F
Best forHomes, cabins, irrigation, small offices and light commercial buildings, including tanks and cisterns below the pump.
View Ocelot 25 View Ocelot 60
TIGERFLOW Ocelot Duplex booster skid, two pumps with stainless manifolds

Ocelot Duplex

Two pumps, one skid, lead-lag

144 GPMMax flow
99 psiMax boost
2 x 2 HP208-230V 1Ph/3Ph
2-1/2 inGrooved

Two Ocelot 60 pumps on 304 stainless piping with isolation valves on each pump. Constant pressure control runs them lead-lag with automatic alternation, so the pair shares the wear and the second pump picks up as demand climbs. Rated 70 GPM at 61 psi.

  • 2 x Ocelot 60 with integrated drives
  • 304 stainless suction and discharge headers
  • Individual pump isolation valves
  • Options: bladder tank, gauges, flange adapters
Best forMultifamily and light commercial buildings that need a pump in reserve.
View Ocelot Duplex
TIGERFLOW Tigercub simplex booster system with CD vertical multistage pump, VFD and disconnect

Tigercub Simplex Systems

Packaged, UL / cUL listed

22-154 GPMMax flow
45-305 psiMax boost
1-7-1/2 HPTEFC motor
UL 508ADisconnect panel

A TIGERFLOW CD vertical multistage pump on a stainless base and manifold, with a variable frequency drive, UL 508A listed disconnect panel and every valve already piped, prefabricated and factory tested as one UL / cUL listed packaged pumping system. Five pump sizes, 32 models.

  • CD3, CD5, CD10, CD15 and CD20 pumps
  • Non-slam stainless check valve, low suction alarm
  • Liquid-filled gauges, vibration isolators
  • Union-ball valves, 1-1/4 in or 2 in
Best forApartment buildings, hotels, municipal sites and shopping centers that need high boost from one pump.
View Tigercub CD5

Every Tigercub Size

TIGERFLOW Booster Model Comparison

Every TIGERFLOW booster on one table. Max boost is the pressure added at zero flow; boost falls as flow rises (see Performance).

Model Pumps Max flow Max boost HP Power Connections Suction
Ocelot 25 1 24 GPM 70 psi 1 120V 1Ph 1 in NPT Self-priming
Ocelot 60 1 77 GPM 99 psi 2 208-230V 1Ph or 3Ph 2 in NPT Self-priming
Ocelot Duplex 2 144 GPM 99 psi 2 x 2 208-230V 1Ph or 3Ph 2-1/2 in grooved Self-priming
Tigercub CD3 1 22 GPM 76-278 psi 1-5 208-230V 1Ph; 208-230V or 460V 3Ph 1-1/4 in Flooded or pressurized
Tigercub CD5 1 44 GPM 45-305 psi 1-7-1/2 208-230V 1Ph; 208-230V or 460V 3Ph 1-1/4 in Flooded or pressurized
Tigercub CD10 1 74 GPM 45-207 psi 2-7-1/2 208-230V 1Ph; 208-230V or 460V 3Ph 2 in Flooded or pressurized
Tigercub CD15 1 127 GPM 53-113 psi 5-7-1/2 208-230V 1Ph; 208-230V or 460V 3Ph 2 in Flooded or pressurized
Tigercub CD20 1 154 GPM 56-85 psi 5-7-1/2 208-230V 1Ph; 208-230V or 460V 3Ph 2 in Flooded or pressurized

Ocelot data from the TIGERFLOW Ocelot Simplex and Duplex booster brochure (April 2025); Tigercub data from the TIGERFLOW Tigercub and CD Series catalogs. 7-1/2 HP Tigercub builds are three phase only.

Quick rule. Water below the pump, or a 120V home: Ocelot. A building that needs a pump in reserve under 144 GPM: Ocelot Duplex. Boost over 99 psi, or a specification that calls for a UL listed package with a disconnect: Tigercub, sized by flow (CD3 to CD20).

TIGERFLOW vs DAB, DuraMAC, Franklin Electric and Grundfos

We sell every line below, so we can be straight about fit. Specifications are taken from our own product pages for each brand.

Home and light commercial boosters

Specification TIGERFLOW Ocelot 25 / 60 DAB Esybox Mini3 / Esybox A.Y. McDonald DuraMAC Residential / Light Commercial Franklin Electric VersaBoost Pro Grundfos SCALA2
Max flow 24 / 77 GPM 22 / 32 GPM 20 / 35 GPM 18 or 25 GPM 20.7 GPM
Max boost 70 / 99 psi 80 / 92 psi 35-70 / 40-78 psi 80 psi 147 ft (63 psi)
Motor 1 / 2 HP 1.1 / 2.1 HP 1/2-1 / 1-1-1/2 HP 0.8-1.1 HP 0.74 HP
Power 120V 1Ph / 208-230V 1Ph or 3Ph 115-127V or 208-240V 1Ph / 230V 1Ph 120V or 230V 1Ph / 230V 1Ph 120V or 208-240V 1Ph 115V or 230V
Suction Self-priming to 9 ft, up to 25 ft Self-priming to 26 ft Not stated on our listing Up to 25 ft suction lift Self-priming to 26 ft
Connections 1 in / 2 in NPT 1 in NPT 1 in / 1 and 1-1/4 in NPT 1 in NPT Not stated on our listing
Location IPX6 outdoor-rated cover Indoor; outdoor with Esycover Indoor NEMA 3R indoor or outdoor Outdoor rated
Warranty 12 months from purchase 24 months from purchase 3 years from installation 36 months from purchase 12 months from purchase

Verdict. The Ocelot 60 carries the most flow in this group, 77 GPM, and up to 99 psi, on single or three phase, so one unit covers a large home, a small office or an irrigation job that would need a larger booster from the other brands. DAB Esybox and Mini3 lead on self-priming depth (26 ft) and carry a 24-month warranty. DuraMAC Residential and Light Commercial carry the longest warranty, 3 years from installation. Franklin VersaBoost Pro carries 36 months and groups four units wirelessly. Grundfos SCALA2 is rated for outdoor installation and pairs with the Grundfos GO app.

Commercial packaged boosters

Specification TIGERFLOW Tigercub TIGERFLOW Ocelot Duplex DAB Esybox Max Duplex A.Y. McDonald DuraMAC IQ1000 Simplex Franklin Electric Inline SpecPAK Grundfos Hydro Multi-E Duplex (CRE 3 / CRE 5)
Pumps per system 1 2 2 1 2, 3 or 4 2
Max system flow 22-154 GPM by pump size 144 GPM 126-153 GPM 80-140 GPM 92-329 GPM 89 GPM
Max boost 45-305 psi 99 psi 83-136 psi 56-150 psi 72-113 psi 205 psi
Motor 1-7-1/2 HP 2 x 2 HP 2 x 2.7-4.7 HP 3-10 HP 1-1/2-3 HP per pump 1-5 HP per pump
Power 208-230V 1Ph; 208-230V or 460V 3Ph 208-230V 1Ph or 3Ph 208-240V 1Ph or 460V 3Ph 208-230V 1Ph/3Ph or 460V 3Ph 208-230V 1Ph 200-240V 1Ph or 3Ph; 440-480V 3Ph
Connections 1-1/4 or 2 in union-ball valves 2-1/2 in grooved 2 in NPT manifold 2 in 3 or 4 in grooved 2 in NPT manifolds
Control VFD and UL 508A listed disconnect panel Drive in each pump, lead-lag with alternation Drive in each pump, wireless grouping, no panel Yaskawa iQpump 1000 drive VFD per pump, 7 in touchscreen PLC, UL 508A panel Integrated VFD, IE5 motors
Listings UL / cUL packaged system; CD pump NSF/ANSI 61 and 372 Not stated on our listing NSF/ANSI 61 and 372, UL, CSA NSF/ANSI/CAN 61, NSF/ANSI 372 NSF/ANSI/CAN 61 and 372 UL listed; NSF 61/372 on most builds
Warranty 12 months from purchase 12 months from purchase 24 months from purchase 1 year from installation or 2 years from manufacture 12 months install or 24 months manufacture; 36 with start-up form 12 months from purchase

Verdict. Tigercub adds the most pressure from a single pump in our booster range, to 305 psi on the CD5-20, as a UL / cUL listed package with its own disconnect, on single-phase power up to 5 HP; it is a simplex, so it has no standby pump. The Ocelot Duplex is the compact way to get a reserve pump under 144 GPM. DAB Esybox Max carries a 24-month warranty and grows to four pumps without a panel. DuraMAC IQ1000 moves more water per pump, to 140 GPM. Franklin Inline SpecPAK wins where the specification calls for a touchscreen PLC panel, grooved 3 or 4 in headers and up to four pumps. Grundfos Hydro Multi-E adds up to 205 psi in a duplex with IE5 motors.

Which TIGERFLOW Booster Do You Need?

Typical selections by application. Demand figures are estimates; send us the fixture count, floors and inlet pressure for an engineering-led selection.

Application Typical demand Recommended Notes
Home on low city pressure, 120V 8-15 GPM at 20-35 psi boost Ocelot 25 Plugs into a 120V outlet; tank and check valves built in.
Home, cabin or RV fed from a tank or cistern 8-15 GPM, tank below the pump Ocelot 25 Self-priming to 9 ft as standard.
Large home, small office, irrigation zone 20-40 GPM at up to 60 psi boost Ocelot 60 208-230V single or three phase.
Small apartment building or school wing that needs standby 40-100 GPM at up to 60 psi boost Ocelot Duplex Lead-lag; one pump runs while the other rests.
Mid-rise apartments or hotel, high boost, low flow 15-40 GPM at 80-250 psi boost Tigercub CD3 or CD5 UL / cUL listed package; flooded suction.
Apartment building or hotel, moderate flow 30-70 GPM at 40-180 psi boost Tigercub CD10 2 in valves; 7-1/2 HP builds are three phase.
Shopping center, municipal site, low-rise campus 50-150 GPM at 30-100 psi boost Tigercub CD15 or CD20 Highest flow in the TIGERFLOW range.
Standby required above 144 GPM, or larger flanged headers 150-420 GPM DuraMAC IQ1000 Duplex or Triplex Or a TIGERFLOW duplex built to order; ask us.

Sizing a TIGERFLOW Booster

Two numbers pick the model: required boost and peak flow. Get both right and the size follows.

1. Required boost

Setpoint = pressure needed at the highest fixture + 0.433 psi per foot of elevation to it + friction losses. Required boost = setpoint − inlet pressure measured at peak demand. From a tank at pump level, nothing arrives with pressure; with a tank below the pump, add 0.433 psi per foot of lift.

2. Peak flow

Use fixture units on Hunter’s curve (IPC Table 604.3) for residential and multifamily, and the IAPMO Water Demand Calculator for light commercial. Peak simultaneous demand sizes the booster, never the total connected load. Our calculator gives both the code figure and a realistic peak.

Worked example: 4-story, 24-unit apartment building. Top fixture needs 30 psi, 45 ft above the pump: 45 × 0.433 = 19.5 psi. Friction 10 psi. Setpoint = 30 + 19.5 + 10 = 59.5, call it 60 psi. City main at the morning peak: 20 psi. Required boost = 60 − 20 = 40 psi at a peak of 30 GPM.

The Tigercub CD5-4 adds 41 psi at 33 GPM, too close at the top of the range. The CD5-6 (2 HP) adds 64 psi at 33 GPM, a 24 psi margin, with the boost at 44 percent of its 90 psi maximum. The Ocelot 60 adds 61 psi at its rated 35 GPM and also covers this duty in a smaller unit; choose the Tigercub where the specification calls for a UL listed package and disconnect, or the Ocelot Duplex where the building needs a pump in reserve.

3. Check the limits

Ocelot: water 32 to 167°F, ambient 32 to 104°F, self-priming to 9 ft standard. Tigercub: flooded or pressurized suction, incoming plus added pressure within the CD pump’s 362 psi rating. If the required boost lands past 70 percent of the model’s maximum, step up a model. Keep static pressure at the lowest fixtures under 80 psi, with pressure-reducing valves where needed.

Booster Sizing CalculatorPressure Tank Calculator

TIGERFLOW Booster Performance

Pressure added by the pump at full speed, in psi. Read across at your peak flow; the figure must exceed your required boost with margin. The drive holds lower pressures by running slower.

Ocelot: pressure added (psi)

TIGERFLOW Ocelot 25, Ocelot 60 and Ocelot Duplex booster performance chart
Model 0 GPM (Shut-off) Rated flow Pressure added at rated flow Max flow
Ocelot 25 70 13 GPM 39 24 GPM
Ocelot 60 99 35 GPM 61 77 GPM
Ocelot Duplex 99 70 GPM 61 144 GPM

From the performance table in the TIGERFLOW Ocelot Simplex and Duplex booster brochure (April 2025): shut-off 164 ft (Ocelot 25) and 230 ft (Ocelot 60 and Duplex); rated 92 ft and 141 ft. TIGERFLOW prints no head at maximum flow, so no pressure is shown there. The brochure chart is schematic.

Tigercub: pressure added (psi), pump at full speed

Pump size Models HP Max boost (shut-off) Best operating range Max flow
CD3 7 1-5 76-278 6.6-22 GPM 22 GPM
CD5 12 1-7-1/2 45-305 13.2-44 GPM 44 GPM
CD10 8 2-7-1/2 45-207 26.4-74 GPM 74 GPM
CD15 3 5-7-1/2 53-113 44-127 GPM 127 GPM
CD20 2 5-7-1/2 56-85 57.2-154 GPM 154 GPM

Open a pump size for every build. A model offered at two HP sizes runs on the same curve. The CD15 table reads to 126 GPM, the last regular digitized flow; its curve ends at 127 GPM.

Tigercub CD3 · 7 models · best operating range 6.6 to 22 GPM
Model 0 GPM (Shut-off) 7 GPM 11 GPM 17 GPM 22 GPM (Max)
CD3-5 · 1 HP 76 72 68 57 39
CD3-7 · 1-1/2 HP 107 104 98 80 55
CD3-10 · 2 HP 153 149 142 114 78
CD3-12 · 3 HP 184 178 168 137 94
CD3-14 · 3 HP 215 208 198 159 109
CD3-16 · 3 HP 247 239 226 186 129
CD3-16 · 5 HP 247 239 226 186 129
CD3-18 · 5 HP 278 270 256 209 143
Tigercub CD5 · 12 models · best operating range 13.2 to 44 GPM
Model 0 GPM (Shut-off) 14 GPM 22 GPM 33 GPM 44 GPM (Max)
CD5-3 · 1 HP 45 42 39 29 16
CD5-4 · 1-1/2 HP 60 56 52 41 23
CD5-6 · 2 HP 90 85 80 64 39
CD5-7 · 3 HP 106 100 93 75 45
CD5-9 · 3 HP 137 130 121 97 58
CD5-10 · 3 HP 151 144 134 108 65
CD5-12 · 5 HP 183 172 163 130 79
CD5-13 · 5 HP 198 188 176 140 86
CD5-15 · 5 HP 228 219 204 161 101
CD5-16 · 5 HP 244 232 217 173 108
CD5-18 · 7-1/2 HP 275 260 242 195 122
CD5-20 · 7-1/2 HP 305 291 269 217 135
Tigercub CD10 · 8 models · best operating range 26.4 to 74 GPM
Model 0 GPM (Shut-off) 28 GPM 42 GPM 56 GPM 74 GPM (Max)
CD10-2 · 2 HP 45 42 39 32 19
CD10-3 · 3 HP 68 64 58 49 33
CD10-4 · 3 HP 90 85 78 66 44
CD10-4 · 5 HP 90 85 78 66 44
CD10-5 · 5 HP 113 105 98 84 57
CD10-6 · 5 HP 137 129 118 102 69
CD10-7 · 7-1/2 HP 160 151 141 120 81
CD10-8 · 7-1/2 HP 184 173 161 139 93
CD10-9 · 7-1/2 HP 207 195 182 156 106
Tigercub CD15 · 3 models · best operating range 44 to 127 GPM
Model 0 GPM (Shut-off) 46 GPM 72 GPM 96 GPM 126 GPM (Max)
CD15-2 · 5 HP 53 51 48 41 28
CD15-3 · 5 HP 80 77 74 66 44
CD15-3 · 7-1/2 HP 80 77 74 66 44
CD15-4 · 7-1/2 HP 113 105 98 87 60
Tigercub CD20 · 2 models · best operating range 57.2 to 154 GPM
Model 0 GPM (Shut-off) 58 GPM 88 GPM 116 GPM 154 GPM (Max)
CD20-2 · 5 HP 56 53 50 45 30
CD20-3 · 7-1/2 HP 85 81 76 67 46

Read from the published CD curves in the TIGERFLOW CD Series Vertical Multistage Pumps catalog (60 Hz, 3500 RPM), digitized from the catalog’s vector curve data and rounded down to whole psi. Zero flow is the shut-off point, a ceiling and not a working point. The best operating range is the solid section of each published curve. Head in feet = psi × 2.31. Request the manufacturer curve for your duty point before specifying.

Incoming pressure turns into extra flow. On a city main the pump only adds the difference between the main and your setpoint, so it runs further right on its curve and delivers more than its rated flow at the same setpoint. Size against the main at the morning peak, not at noon.

What Sets TIGERFLOW Boosters Apart

The design choices behind the Ocelot and Tigercub, and why they matter on an installation.

Constant Pressure

Every model runs on a variable speed drive that holds one setpoint as fixtures open and close, so pressure stays steady on the top floor without hard starts.

Permanent Magnet Ocelot

The Ocelot pairs a permanent magnet motor with its own drive and keypad. Low-flow detection slows or stops the pump when demand drops.

Self-Priming Ocelot

Ocelot pumps self-prime to 9 ft as standard and up to 25 ft by installation, so they draw from tanks and cisterns below the pump.

Built-In Tank and Check Valves

Ocelot 25 and 60 carry an expansion tank for leak loads and check valves on suction and discharge, which keeps the installation to piping and power.

One UL / cUL Listed Package

Tigercub ships prefabricated and factory tested as one listed packaged pumping system (QCZJ), with a UL 508A listed disconnect panel and single source responsibility.

High Head from One Pump

The CD vertical multistage pump reaches 305 psi of boost from a single 7-1/2 HP motor on the CD5-20, within a 362 psi pump rating.

Stainless Throughout

AISI 304 stainless Ocelot bodies; 304/316 stainless CD impellers on a stainless base and manifold; 304 stainless headers on the Ocelot Duplex.

Protection Built In

Tigercub includes a low suction or low-level alarm, a non-slam center-guided check valve, liquid-filled gauges and vibration isolators as standard.

TIGERFLOW Booster Accessories and Spare Parts

The factory options that complete an installation, and the parts that keep it running. Order them with the booster so the job ships together.

CD pump ends (wet ends) are listed by model for a full Tigercub rebuild: CD5 pump end. Send the serial number and we match the part.

Why Buy TIGERFLOW Boosters from Watermain Supply

Engineering-Led Sizing

Every selection is checked against TIGERFLOW’s published performance for your flow, setpoint and inlet pressure before it ships. Factory submittal on request.

Same-Day Quote

Send the building numbers in the morning and get a sized selection, accessories and lead time back the same day.

Multi-Brand Honesty

We also sell DAB, A.Y. McDonald DuraMAC, Franklin Electric and Grundfos boosters. If TIGERFLOW is not the right fit, we will say so and quote the one that is.

Account Terms Available

Net-30 for qualified contractor, property management and municipal accounts. PO and credit applications handled in-house.

Parts and Aftermarket

Seals, pump ends, motors, tanks and purge valves for the Tigercub and Ocelot, matched by model and serial number.

Texas to Texas

A Dallas-built booster from a Houston supplier, with Gulf Coast service and one order for the booster, tank and accessories.

Frequently Asked Questions

Common questions from homeowners, contractors and engineers selecting a TIGERFLOW booster.

What warranty comes with TIGERFLOW Ocelot and Tigercub boosters?

Ocelot 25, Ocelot 60, Ocelot Duplex and every Tigercub simplex system are covered for 12 months from the date of purchase under TIGERFLOW’s published warranty terms.

Which TIGERFLOW booster is right for a single-family home?

The Ocelot 25 on 120V single phase: 70 PSI of boost at zero flow, 39 PSI at its rated 13 GPM and 24 GPM maximum, with a built-in expansion tank and check valves. For a large home or a small office on 208-230V, the Ocelot 60 adds 61 PSI at 35 GPM.

Can the Ocelot pull water from a tank or cistern below the pump?

Yes. Ocelot pumps are self-priming to 9 ft as standard and up to 25 ft depending on installation conditions. Tigercub systems need a flooded suction or a pressurized supply.

How much pressure can a Tigercub add?

Up to 305 PSI at zero flow on the Tigercub CD5-20, from a single 7-1/2 HP pump. The CD Series pump is rated to 362 PSI working pressure, so incoming plus added pressure must stay within that rating.

What comes with a Tigercub simplex booster system?

The CD vertical multistage pump and TEFC motor, a variable frequency drive, a UL 508A listed disconnect panel, a non-slam stainless check valve, a low suction or low-level alarm, liquid-filled gauges, vibration isolators and union-ball valves on suction and discharge, factory tested as one UL / cUL listed packaged pumping system.

Does a Tigercub need a pressure tank?

TIGERFLOW recommends its 2-gallon, 150 PSI diaphragm expansion tank to cut cycling under leak loads; larger tanks to 44 gallons are options. The Ocelot 25 and Ocelot 60 have an expansion tank built in.

Which TIGERFLOW booster gives me a standby pump?

The Ocelot Duplex: two Ocelot 60 pumps on one stainless skid, lead-lag with automatic alternation, up to 144 GPM. Tigercub is a simplex package; TIGERFLOW builds duplex and larger systems to order.

How does TIGERFLOW compare with DAB, DuraMAC, Franklin Electric and Grundfos?

Tigercub adds the most pressure from one pump in our booster range, to 305 PSI, as a UL / cUL listed package. DAB carries a 24-month warranty, DuraMAC IQ1000 carries more flow per pump, Franklin Inline SpecPAK brings a touchscreen PLC and grooved headers, and Grundfos Hydro Multi-E adds 205 PSI in a duplex. We sell all of them and will tell you which fits.

Are TIGERFLOW pumps approved for drinking water?

The TIGERFLOW CD vertical multistage pump inside every Tigercub is certified to NSF/ANSI 61 and 372. Ask us for the certification status of the Ocelot for your application before ordering it for potable service.

Who makes TIGERFLOW boosters?

TIGERFLOW Systems, LLC of Dallas, Texas, which has designed and manufactured pumping equipment for more than 35 years: domestic water boosters, HVAC pumping systems and engineered pump packages.

Ready to Size Your TIGERFLOW Booster?

Send your flow or fixture count, floors, inlet pressure and available power. We will reply the same day with a sized Ocelot or Tigercub selection, accessories and ship date.

Technical data on this page is taken from TIGERFLOW Systems product literature and is subject to change by the manufacturer. Confirm against the current installation manual before specifying.
TIGERFLOW, Ocelot and Tigercub are trademarks of TIGERFLOW Systems, LLC; DAB, Esybox, Esybox Mini3 and Esybox Max of DAB Pumps S.p.A.; Grundfos, SCALA2 and Hydro Multi-E of Grundfos Holding A/S; Franklin Electric, SpecPAK and VersaBoost of Franklin Electric Co., Inc.; A.Y. McDonald, DuraMAC and IQ1000 of A.Y. McDonald Mfg. Co. All are used here for product identification only.
Watermain Supply is a DBA of E4 Industrial LLC, an independent industrial supplier based in Houston, Texas.