Taco · Variable Frequency Drive with Bypass, Vertical Panel
SmartDrive VP
12 builds: 7.5 to 60 HP at 200-240V and 15 to 125 HP at 480V and 525-600V three phase, with bypass.
Variable Frequency Drive for Pumps
200-240V / 480V / 525-600V Supply
NEMA 1 Vertical Panel
BACnet, Modbus RTU, N2, FLN Built In
Dual DC-Link Chokes (5% Reactor Equivalent)
IEEE 519-1992 Support
+TSL Pump Logic Option
51-143 lb Weight
Overview
The SmartDrive VP is Taco’s vertical panel drive: a SmartDrive HVAC (Danfoss VLT FC 102) with a standard 3-contactor bypass in a slim vertical NEMA 1 panel that takes less horizontal wall space than a traditional panel, with the same components and performance. A 24 VDC switch mode control power supply on the P2 to P4 panel sizes, and a voltage sensing relay on P5, protect the contactors against brown-outs and phase loss.
- Standard 3-contactor electromechanical bypass
- Fused disconnect or circuit breaker; Class 20 overload; UL / cUL
- Fan-cooled through a back channel; IBC and OSHPD seismic certifications
- +TSL pump control option; BACnet in every drive
What Ships and What It Needs to Run
Included: the drive, in its vertical panel with 3-contactor bypass, disconnect and overload.
Set when you order: motor HP, voltage and full load amps; the +TSL pump control option and any option cards.
Wiring: line, motor and control wiring, disconnect and branch protection to code, provided on site.
Ships: about 51-143 lb by frame.
Genuine Taco equipment, factory-new in original packaging — sold and supported by Watermain Supply, an independent industrial supplier. Watermain Supply is an Authorized Taco Distributor.
Taco Warranty
Covered by Taco’s limited warranty. The Taco documents for this product do not state the term; ask us and we will confirm the current Taco terms before you order.
Specifications
| Drive |
Danfoss VLT HVAC platform, supplied and supported by Taco |
| Supply frequency |
50/60 Hz |
| Displacement power factor |
Above 0.98 |
| I/O |
6 digital inputs, 2 digital outputs, 2 pulse inputs, 2 analog inputs, 1 analog output, 2 Form C relays |
| Electrical configuration |
3-contactor bypass with drive fusing and main disconnect (5 kA SCCR) or main fusing and disconnect (100 kA SCCR) |
| Enclosure |
NEMA Type 1 / IP21 |
| Ambient |
14 to 113°F up to 3,300 ft |
From the Taco submittal data sheets, catalog and instruction sheets.
Frames, HP and Voltage
Each build on this listing is one frame size at one supply voltage, covering the motor HP range shown. Tell us the motor HP, voltage and full load amps and we will set the drive to the motor.
| Frame |
200-240V 3 ph |
480V 3 ph |
525-600V 3 ph |
Max weight |
| B1 |
7.5-15 HP |
15-25 HP |
15-25 HP |
51 lb |
| B2 |
20 HP |
30-40 HP |
30-40 HP |
60 lb |
| C1 |
25-30 HP |
50-75 HP |
50-75 HP |
99 lb |
| C2 |
40-60 HP |
100-125 HP |
100-125 HP |
143 lb |
From the Taco SmartDrive VP submittal 301-2134. Weight is the maximum for the frame.
Before You Buy — The Limits That Decide the Fit
| Motor |
Pick the frame whose HP range at your supply voltage covers the motor nameplate HP |
| Supply |
Three phase supply as listed; check the voltage before ordering |
| Location |
Indoor unless the enclosure rating says otherwise; keep within the ambient limits in the specifications |
| Control |
Add the +TSL option for factory-programmed Delta-P, Delta-T or domestic booster pump control |
Installation Notes
- Install, wire and start up the drive per the Taco SmartDrive IOM and the Danfoss VLT manuals in the Data Sheet tab
- Complete the Taco SmartDrive start-up checklist at commissioning
- Size the line protection and wiring to the drive input current and local code
- Run the start-up wizard or quick menu to enter the motor nameplate data before running the pump
From the Taco SmartDrive VP / SP bypass panel installation manual and SmartDrive +TSL IOM 302-370.
Applications
Variable speed control of HVAC and domestic water pumps: Delta-P and Delta-T hydronic pumping and domestic water booster sets, 1 to 3 pumps with lead / lag.