Taco SKV SelfSensing Vertical In-Line Pump - Variable Speed, Close-Coupled

HP - Speed: 1 1/2 HP - 1760 RPM
Suction x Discharge: 1-1/2 x 1-1/2 in
Model: SKV1506D

Product variant with selected options does not exist!

Price
$13,343.97
Coupon 5% off applied automatically in your cart. No code needed.
SKU: SKV1506D-1760-1.5HP
Weight : 196.0 lb
Loading locations...
Free Shipping $499 or more
Skip the chatbot. Talk to an expert.
1-888.510.4036 · Same-day shipping available
Description
Taco · SelfSensing Vertical In-Line Pump, Close-Coupled
SKV Series
118 US builds: 22 pump sizes, 1 1/2-60 HP, 1-1/2 to 8 in flanges, 1760 to 3500 RPM, 60 Hz.
1 1/2-60 HP Variable Speed
1760 or 3500 RPM, 60 Hz
1-1/2 to 8 in Flanges
SelfSensing Drive, No Remote Sensors
175 psig Std, 300 psig with 250# Flanges
250°F Max Liquid
Bronze-Fitted
DOE PEI 0.79-0.96
15-33.5 x 6.6-19.2 x 20.4-40.8 in
150-1438 lb Weight
Overview

The SKV is Taco’s SelfSensing vertical in-line pump, close-coupled. It is the KV pump paired with a Taco variable frequency drive running SelfSensing ProBalance software. The drive reads the pump’s own operating point, so it needs no remote sensors or extra wiring, and it lets the installer balance the system by reducing pump speed rather than throttling a valve. One pump serves constant flow chiller and boiler duty or secondary variable flow duty. Each build on this listing is one pump size at one speed with one motor and drive HP; Taco trims the impeller to your duty point when the pump is ordered.

  • Control modes: constant flow, variable flow (flow compensation), constant pressure and duplex standby alternation
  • BACnet, Modbus RTU, N2 Metasys, FLN Apogee and FC protocol standard
  • Alerts with optional shutdown for no-flow, dry-run and end-of-curve operation
  • Dual DC-link chokes (equal to a 5% AC line reactor), supporting IEEE 519-1992
What Ships and What It Needs to Run

Included: the KV pump and its NEMA JM-frame motor, close-coupled and assembled. The Taco SelfSensing variable frequency drive ships with it, mounted on the pump or for wall mounting.

Set when you order: the impeller diameter for your duty point, motor and drive voltage.

Support stand: optional ductile iron stand, ordered with the pump where the installation calls for it.

Ships by freight: about 150-1438 lb by build; plan for a lift at delivery.

Genuine Taco equipment, factory-new in original packaging — sold and supported by Watermain Supply, an independent industrial supplier. Watermain Supply is an Authorized Taco Distributor.
1-Year Taco Warranty

Covered for 1 year from start-up or 18 months from shipment, whichever comes first, under Taco’s limited warranty for commercial pumps. Taco states that the motor is warranted by the motor manufacturer and that seals are not covered.

Specifications
Pump type Single-stage vertical in-line volute pump, close-coupled, back pull-out
Motor NEMA standard JM-frame motor, ODP or TEFC
Speed 1760 or 3500 RPM by build, 60 Hz
Connections ANSI Class 125 flanges (standard) or Class 250, 1-1/2 to 8 in
Maximum working pressure 175 psig with Class 125 flanges; 300 psig with Class 250 flanges
Maximum liquid temperature 250°F
Mechanical seal John Crane Type 21 for 175 psig; Type 2 for 300 psig
Pump energy index DOE PEI 0.79-0.96 by build
Drive Taco variable frequency drive with SelfSensing ProBalance
Control modes Constant flow, variable flow (flow compensation), constant pressure, duplex standby alternation
Communication BACnet, Modbus RTU, N2 Metasys, FLN Apogee, FC protocol (standard); LonWorks, DeviceNet, Profibus (optional)
Drive I/O 6 digital inputs, 2 digital outputs, 1 analog current output, 2 analog inputs, 2 pulse inputs, 2 Form C relays
Harmonic suppression Dual DC-link chokes, equal to a 5% AC line reactor; supports IEEE 519-1992
Drive ambient -14 to 113°F up to 3,300 ft
Drive enclosure NEMA Type 12 / IP55 or NEMA Type 4X / IP66

From the Taco submittal data sheets, catalog and IOM.

Models & Performance — Will It Do What You Need?

Each block is one flange size at one speed. Every row is one pump size this listing sells, with the motor HP range Taco offers for it, and every figure is the total head in feet the pump adds at the flow heading the column, on the largest impeller Taco offers for that size. Taco trims the impeller to the duty point you order, which brings the curve down to it; the full family of impeller curves for each size is in the image gallery. The SelfSensing drive runs the pump at any speed up to this full-speed curve and follows the system from there.

SKV 1-1/2 x 1-1/2 in, 1760 RPM: 1506D, 1507D, 1 1/2-5 HP, 44-58 ft shut-off, 141 GPM
Model, motor 0 GPM 70 105 141 (Max)
1506D, 1 1/2 HP 44 38 22 —
1507D, 1 1/2-2 HP 58 53 46 34
SKV 1-1/2 x 1-1/2 in, 3500 RPM: 1506D, 1507D, 3-10 HP, 174-230 ft shut-off, 255 GPM
Model, motor 0 GPM 130 190 255 (Max)
1506D, 3-10 HP 174 156 115 —
1507D, 7 1/2-10 HP 230 215 190 147
SKV 2 x 2 in, 1760 RPM: 2006D, 2007D, 2009D, 1 1/2-10 HP, 42-100 ft shut-off, 247 GPM
Model, motor 0 GPM 125 185 247 (Max)
2006D, 1 1/2-2 HP 42 31 — —
2007D, 1 1/2-3 HP 57 49 35 —
2009D, 2-7 1/2 HP 100 93 82 58
SKV 2 x 2 in, 3500 RPM: 2006D, 2007D, 2009D, 5-50 HP, 164-389 ft shut-off, 419 GPM
Model, motor 0 GPM 210 315 419 (Max)
2006D, 5-15 HP 164 135 — —
2007D, 7 1/2-15 HP 222 204 167 —
2009D, 15-50 HP 389 371 340 280
SKV 3 x 3 in, 1760 RPM: 3006D, 3007D, 3009D, 3011D, 3013D, 1 1/2-30 HP, 40-203 ft shut-off, 583 GPM
Model, motor 0 GPM 290 440 583 (Max)
3006D, 1 1/2-2 HP 40 — — —
3007D, 3-5 HP 54 41 — —
3009D, 3-10 HP 97 82 42 —
3011D, 5-15 HP 129 108 55 —
3013D, 10-30 HP 203 196 173 116
SKV 3 x 3 in, 3500 RPM: 3006D, 3007D, 3009D, 5-60 HP, 155-374 ft shut-off, 900 GPM
Model, motor 0 GPM 450 680 900 (Max)
3006D, 5-10 HP 155 78 — —
3007D, 20-40 HP 212 190 130 —
3009D, 30-60 HP 374 345 268 106
SKV 4 x 4 in, 1760 RPM: 4007D, 4009D, 4011D, 4013D, 3-40 HP, 54-193 ft shut-off, 921 GPM
Model, motor 0 GPM 460 690 921 (Max)
4007D, 3-7 1/2 HP 54 34 — —
4009D, 5-15 HP 92 80 57 —
4011D, 10-20 HP 127 110 81 —
4013D, 15-40 HP 193 176 151 98
SKV 4 x 4 in, 3500 RPM: 4007D, 4009D, 15-60 HP, 208-355 ft shut-off, 1,570 GPM
Model, motor 0 GPM 790 1,180 1,570 (Max)
4007D, 15-40 HP 208 158 — —
4009D, 40-60 HP 355 325 265 154
SKV 5 x 5 in, 1760 RPM: 5007D, 5-7 1/2 HP, 54 ft shut-off, 802 GPM
Model, motor 0 GPM 400 600 802 (Max)
5007D, 5-7 1/2 HP 54 46 37 19
SKV 5 x 5 in, 3500 RPM: 5007D, 25-60 HP, 209 ft shut-off, 1,504 GPM
Model, motor 0 GPM 750 1,130 1,504 (Max)
5007D, 25-60 HP 209 183 149 85
SKV 6 x 6 in, 1760 RPM: 6007D, 6009D, 6011D, 6013D, 5-50 HP, 46-191 ft shut-off, 1,960 GPM
Model, motor 0 GPM 980 1,470 1,960 (Max)
6007D, 5-10 HP 46 23 — —
6009D, 10-25 HP 85 73 46 —
6011D, 15-40 HP 121 104 66 —
6013D, 25-50 HP 191 173 141 73
SKV 6 x 6 in, 3500 RPM: 6007D, 40-60 HP, 192 ft shut-off, 2,252 GPM
Model, motor 0 GPM 1,130 1,690 2,252 (Max)
6007D, 40-60 HP 192 176 131 27
SKV 8 x 8 in, 1760 RPM: 8011D, 25-50 HP, 124 ft shut-off, 2,744 GPM
Model, motor 0 GPM 1,370 2,050 2,744 (Max)
8011D, 25-50 HP 124 109 85 37

Head in feet at the flow in GPM heading each column: 50% and 75% of the largest curve in the block, then its end. Bold = the last column that curve reaches; — = beyond its curve. Maximum-impeller curves digitized from the Taco KV 60 Hz performance curves and rounded down. PSI = feet ÷ 2.31.

The 1509 and 2011 sizes are printed on an older curve format that could not be read reliably, or Taco publishes no 60 Hz curve for them: their curves are in the image gallery where Taco publishes one, or email your duty point and we will confirm the selection with Taco.

Before You Buy — The Limits That Decide the Fit
Duty point Pick the size whose curve passes through your flow and head; send it to us and we will confirm the impeller trim with Taco before you order
Liquid Water or other suitable HVAC media; not for hazardous, corrosive or flammable liquids
Mounting Vertical, motor up; consult Taco for horizontal mounting. The pump must always be supported
Priming Fill and vent the pump before starting; never run it dry
Pressure 175 psig with Class 125 flanges; order Class 250 flanges for up to 300 psig
Power Motor and drive voltage set at order; size the supply and protection to the drive
Installation Notes
  • Pumps with smaller motors may hang in the piping when the pipe is supported next to the pump; larger motors need a support under the casing, using the tapped holes in its base
  • Keep piping loads off the pump and let it move with the piping; do not rigidly fix it to the floor, and use vibration isolation pads under floor supports
  • Lift by the motor eye bolts together with the pump adapter, and never cover any part of the motor with insulation
  • Jog the motor to check rotation, open the suction valve, start against a closed discharge valve and open it slowly
  • Do not run for long periods against a closed discharge valve

From the Taco KV Installation, Operation and Maintenance Manual 302-031.

Applications

Constant flow chiller and boiler pumping and secondary variable flow pumping in HVAC systems.

Materials of Construction
Part Bronze-fitted (standard)
Casing Cast iron ASTM A48 Class 30A (125#); ductile iron ASTM A536 65-45-12 (250#)
Cover Cast iron ASTM A48 Class 30A
Impeller Bronze ASTM B584 C83600 or C84400
Shaft Carbon steel
Shaft sleeve Bronze ASTM B584 C92200
Mechanical seal Ceramic / EPT

Options: bronze wear ring, Type 303 stainless sleeve, tungsten carbide or silicon carbide seal faces. From the Taco KV submittal data sheets.