Taco · Vertical In-Line Pump, Close-Coupled
KV Series
201 US builds: 22 pump sizes, 1-60 HP, 1-1/2 to 8 in flanges, 1160 to 3500 RPM, 60 Hz.
1-60 HP Close-Coupled
1160, 1760 or 3500 RPM, 60 Hz
1-1/2 to 8 in Flanges
175 psig Std, 300 psig with 250# Flanges
250°F Max Liquid
Bronze-Fitted, NSF 61 Option
DOE PEI 0.79-0.96
15-33.5 x 6.6-19.2 x 20.4-40.8 in
132-1274 lb Weight
Overview
The KV is Taco’s close-coupled vertical in-line pump for HVAC and industrial service. The pump mounts straight in the pipe line, needs no isolation pads, and the close-coupled design keeps the pump and its standard NEMA JM motor in alignment for longer seal life. Service is from the back: the motor, cover and impeller pull out without disconnecting the pump from the piping. Each build on this listing is one pump size at one speed with one motor HP; Taco trims the impeller to your duty point when the pump is ordered.
- Standard bronze-fitted construction, with an NSF 61 build that uses a stainless steel impeller
- Pressure taps on suction and discharge for checking pump performance
- Standard seal design that takes a range of seal options
- Optional ductile iron support stand, replaceable casing wear ring and 250# flanges
What Ships and What It Needs to Run
Included: the KV pump and its NEMA JM-frame motor, close-coupled and assembled.
Set when you order: the impeller diameter for your duty point, motor voltage, and motor enclosure (ODP or TEFC).
Support stand: optional ductile iron stand, ordered with the pump where the installation calls for it.
Ships by freight: about 132-1274 lb by build; plan for a lift at delivery.
Genuine Taco equipment, factory-new in original packaging — sold and supported by Watermain Supply, an independent industrial supplier. Watermain Supply is an Authorized Taco Distributor.
1-Year Taco Warranty
Covered for 1 year from start-up or 18 months from shipment, whichever comes first, under Taco’s limited warranty for commercial pumps. Taco states that the motor is warranted by the motor manufacturer and that seals are not covered.
Specifications
| Pump type |
Single-stage vertical in-line volute pump, close-coupled, back pull-out |
| Motor |
NEMA standard JM-frame motor, ODP or TEFC |
| Speed |
1160, 1760 or 3500 RPM by build, 60 Hz |
| Connections |
ANSI Class 125 flanges (standard) or Class 250, 1-1/2 to 8 in |
| Maximum working pressure |
175 psig with Class 125 flanges; 300 psig with Class 250 flanges |
| Maximum liquid temperature |
250°F |
| Mechanical seal |
John Crane Type 21 for 175 psig; Type 2 for 300 psig |
| Pump energy index |
DOE PEI 0.79-0.96 by build |
From the Taco submittal data sheets, catalog and IOM.
Models & Performance — Will It Do What You Need?
Each block is one flange size at one speed. Every row is one pump size this listing sells, with the motor HP range Taco offers for it, and every figure is the total head in feet the pump adds at the flow heading the column, on the largest impeller Taco offers for that size. Taco trims the impeller to the duty point you order, which brings the curve down to it; the full family of impeller curves for each size is in the image gallery.
KV 1-1/2 x 1-1/2 in, 1160 RPM: 1507D, 1-1 1/2 HP, 26 ft shut-off, 94 GPM
| Model, motor |
0 GPM |
45 |
70 |
94 (Max) |
| 1507D, 1 HP |
26 |
23 |
20 |
14 |
KV 1-1/2 x 1-1/2 in, 1760 RPM: 1506D, 1507D, 1-5 HP, 44-58 ft shut-off, 141 GPM
| Model, motor |
0 GPM |
70 |
105 |
141 (Max) |
| 1506D, 1-1 1/2 HP |
44 |
38 |
22 |
— |
| 1507D, 1-2 HP |
58 |
53 |
46 |
34 |
KV 1-1/2 x 1-1/2 in, 3500 RPM: 1506D, 1507D, 3-15 HP, 174-230 ft shut-off, 255 GPM
| Model, motor |
0 GPM |
130 |
190 |
255 (Max) |
| 1506D, 3-10 HP |
174 |
156 |
115 |
— |
| 1507D, 5-15 HP |
230 |
215 |
190 |
147 |
KV 2 x 2 in, 1160 RPM: 2007D, 2009D, 1-2 HP, 25-44 ft shut-off, 189 GPM
| Model, motor |
0 GPM |
95 |
140 |
189 (Max) |
| 2007D, 1 HP |
25 |
20 |
11 |
— |
| 2009D, 1-2 HP |
44 |
40 |
32 |
15 |
KV 2 x 2 in, 1760 RPM: 2006D, 2007D, 2009D, 1-10 HP, 42-100 ft shut-off, 247 GPM
| Model, motor |
0 GPM |
125 |
185 |
247 (Max) |
| 2006D, 1-2 HP |
42 |
31 |
— |
— |
| 2007D, 1-3 HP |
57 |
49 |
35 |
— |
| 2009D, 2-7 1/2 HP |
100 |
93 |
82 |
58 |
KV 2 x 2 in, 3500 RPM: 2006D, 2007D, 2009D, 3-50 HP, 164-389 ft shut-off, 419 GPM
| Model, motor |
0 GPM |
210 |
315 |
419 (Max) |
| 2006D, 3-15 HP |
164 |
135 |
— |
— |
| 2007D, 7 1/2-15 HP |
222 |
204 |
167 |
— |
| 2009D, 15-50 HP |
389 |
371 |
340 |
280 |
KV 3 x 3 in, 1160 RPM: 3007D, 3009D, 3011D, 3013D, 1-10 HP, 23-92 ft shut-off, 377 GPM
| Model, motor |
0 GPM |
190 |
285 |
377 (Max) |
| 3007D, 1-1 1/2 HP |
23 |
18 |
— |
— |
| 3009D, 1-3 HP |
43 |
36 |
20 |
— |
| 3011D, 1 1/2-5 HP |
55 |
47 |
25 |
— |
| 3013D, 3-10 HP |
92 |
89 |
79 |
55 |
KV 3 x 3 in, 1760 RPM: 3006D, 3007D, 3009D, 3011D, 3013D, 1-30 HP, 40-203 ft shut-off, 583 GPM
| Model, motor |
0 GPM |
290 |
440 |
583 (Max) |
| 3006D, 1-2 HP |
40 |
— |
— |
— |
| 3007D, 2-5 HP |
54 |
41 |
— |
— |
| 3009D, 3-10 HP |
97 |
82 |
42 |
— |
| 3011D, 5-15 HP |
129 |
108 |
55 |
— |
| 3013D, 7 1/2-30 HP |
203 |
196 |
173 |
116 |
KV 3 x 3 in, 3500 RPM: 3006D, 3007D, 3009D, 5-60 HP, 155-374 ft shut-off, 900 GPM
| Model, motor |
0 GPM |
450 |
680 |
900 (Max) |
| 3006D, 5-15 HP |
155 |
78 |
— |
— |
| 3007D, 15-40 HP |
212 |
190 |
130 |
— |
| 3009D, 25-60 HP |
374 |
345 |
268 |
106 |
KV 4 x 4 in, 1160 RPM: 4007D, 4009D, 4011D, 4013D, 1-15 HP, 24-84 ft shut-off, 661 GPM
| Model, motor |
0 GPM |
330 |
495 |
661 (Max) |
| 4007D, 1-2 HP |
24 |
13 |
— |
— |
| 4009D, 1 1/2-5 HP |
41 |
34 |
21 |
— |
| 4011D, 3-7 1/2 HP |
56 |
47 |
31 |
— |
| 4013D, 3-15 HP |
84 |
75 |
61 |
33 |
KV 4 x 4 in, 1760 RPM: 4007D, 4009D, 4011D, 4013D, 2-40 HP, 54-193 ft shut-off, 921 GPM
| Model, motor |
0 GPM |
460 |
690 |
921 (Max) |
| 4007D, 2-7 1/2 HP |
54 |
34 |
— |
— |
| 4009D, 5-15 HP |
92 |
80 |
57 |
— |
| 4011D, 7 1/2-25 HP |
127 |
110 |
81 |
— |
| 4013D, 15-40 HP |
193 |
176 |
151 |
98 |
KV 4 x 4 in, 3500 RPM: 4007D, 4009D, 15-60 HP, 208-355 ft shut-off, 1,570 GPM
| Model, motor |
0 GPM |
790 |
1,180 |
1,570 (Max) |
| 4007D, 15-40 HP |
208 |
158 |
— |
— |
| 4009D, 40-60 HP |
355 |
325 |
265 |
154 |
KV 5 x 5 in, 1160 RPM: 5007D, 1-3 HP, 24 ft shut-off, 535 GPM
| Model, motor |
0 GPM |
270 |
400 |
535 (Max) |
| 5007D, 1-3 HP |
24 |
21 |
16 |
8 |
KV 5 x 5 in, 1760 RPM: 5007D, 3-7 1/2 HP, 54 ft shut-off, 802 GPM
| Model, motor |
0 GPM |
400 |
600 |
802 (Max) |
| 5007D, 3-7 1/2 HP |
54 |
46 |
37 |
19 |
KV 5 x 5 in, 3500 RPM: 5007D, 25-60 HP, 209 ft shut-off, 1,504 GPM
| Model, motor |
0 GPM |
750 |
1,130 |
1,504 (Max) |
| 5007D, 25-60 HP |
209 |
183 |
149 |
85 |
KV 6 x 6 in, 1160 RPM: 6007D, 6009D, 6011D, 6013D, 1 1/2-25 HP, 21-84 ft shut-off, 1,349 GPM
| Model, motor |
0 GPM |
670 |
1,010 |
1,349 (Max) |
| 6007D, 1 1/2-3 HP |
21 |
9 |
— |
— |
| 6009D, 3-7 1/2 HP |
37 |
31 |
18 |
— |
| 6011D, 5-10 HP |
53 |
45 |
26 |
— |
| 6013D, 7 1/2-25 HP |
84 |
75 |
58 |
29 |
KV 6 x 6 in, 1760 RPM: 6007D, 6009D, 6011D, 6013D, 5-50 HP, 46-191 ft shut-off, 1,960 GPM
| Model, motor |
0 GPM |
980 |
1,470 |
1,960 (Max) |
| 6007D, 5-10 HP |
46 |
23 |
— |
— |
| 6009D, 7 1/2-25 HP |
85 |
73 |
46 |
— |
| 6011D, 15-40 HP |
121 |
104 |
66 |
— |
| 6013D, 25-50 HP |
191 |
173 |
141 |
73 |
KV 6 x 6 in, 3500 RPM: 6007D, 30-60 HP, 192 ft shut-off, 2,252 GPM
| Model, motor |
0 GPM |
1,130 |
1,690 |
2,252 (Max) |
| 6007D, 30-60 HP |
192 |
176 |
131 |
27 |
KV 8 x 8 in, 1160 RPM: 8011D, 7 1/2-20 HP, 54 ft shut-off, 1,779 GPM
| Model, motor |
0 GPM |
890 |
1,330 |
1,779 (Max) |
| 8011D, 7 1/2-20 HP |
54 |
48 |
38 |
18 |
KV 8 x 8 in, 1760 RPM: 8011D, 20-50 HP, 124 ft shut-off, 2,744 GPM
| Model, motor |
0 GPM |
1,370 |
2,050 |
2,744 (Max) |
| 8011D, 20-50 HP |
124 |
109 |
85 |
37 |
Head in feet at the flow in GPM heading each column: 50% and 75% of the largest curve in the block, then its end. Bold = the last column that curve reaches; — = beyond its curve. Maximum-impeller curves digitized from the Taco KV 60 Hz performance curves and rounded down. PSI = feet ÷ 2.31.
The 1509 and 2011 sizes are printed on an older curve format that could not be read reliably, or Taco publishes no 60 Hz curve for them: their curves are in the image gallery where Taco publishes one, or email your duty point and we will confirm the selection with Taco.
Before You Buy — The Limits That Decide the Fit
| Duty point |
Pick the size whose curve passes through your flow and head; send it to us and we will confirm the impeller trim with Taco before you order |
| Liquid |
Water or other suitable HVAC media; not for hazardous, corrosive or flammable liquids |
| Mounting |
Vertical, motor up; consult Taco for horizontal mounting. The pump must always be supported |
| Priming |
Fill and vent the pump before starting; never run it dry |
| Pressure |
175 psig with Class 125 flanges; order Class 250 flanges for up to 300 psig |
Installation Notes
- Pumps with smaller motors may hang in the piping when the pipe is supported next to the pump; larger motors need a support under the casing, using the tapped holes in its base
- Keep piping loads off the pump and let it move with the piping; do not rigidly fix it to the floor, and use vibration isolation pads under floor supports
- Lift by the motor eye bolts together with the pump adapter, and never cover any part of the motor with insulation
- Jog the motor to check rotation, open the suction valve, start against a closed discharge valve and open it slowly
- Do not run for long periods against a closed discharge valve
From the Taco KV Installation, Operation and Maintenance Manual 302-031.
Applications
HVAC heating and cooling circulation and industrial applications.
Materials of Construction
| Part |
Bronze-fitted (standard) |
NSF 61 build |
| Casing |
Cast iron ASTM A48 Class 30A (125#); ductile iron ASTM A536 65-45-12 (250#) |
Same as standard |
| Cover |
Cast iron ASTM A48 Class 30A |
Cast iron ASTM A48 Class 30A |
| Impeller |
Bronze ASTM B584 C83600 or C84400 |
Stainless steel ASTM A351 |
| Shaft |
Carbon steel |
Carbon steel |
| Shaft sleeve |
Bronze ASTM B584 C92200 |
Bronze ASTM B584 C92200 |
| Mechanical seal |
Ceramic / EPT |
Ceramic / EPT |
Options: bronze wear ring, Type 303 stainless sleeve, tungsten carbide or silicon carbide seal faces. From the Taco KV submittal data sheets.