Taco · Differential Pressure Transmitter, Wet/Wet
DPS629
11 part numbers: 0-25 or 0-100 psid, 4-20 mA, 0-5 or 0-10 VDC output, with or without 3-way valve manifold.
Wet/Wet DP Transmitter
0-25 or 0-100 psid
4-20 mA, 0-5 or 0-10 VDC
±0.5% FS Accuracy
NEMA 4X (IP66) Design
316 / 316L SS Wetted Parts
3-Way Valve Option
Under 1 lb Transmitter
Overview
The DPS629 is Taco’s wet/wet differential pressure transmitter for monitoring the pressure difference across pumps, flow elements, heat exchangers, coils and filters, on air and compatible gases and liquids. Dual pressure sensors convert the pressure change into a standard output signal for two-wire circuits, and the small internal volume and minimal moving parts give fast response. The terminal block and the zero and span adjustments are under the top cover.
- ±0.5% full scale accuracy, including linearity, hysteresis and repeatability
- 4-20 mA standard; 0-5 or 0-10 VDC output models
- Not position sensitive; designed to meet NEMA 4X (IP66)
- Optional 3-way valve manifold with bleed screw
What Ships and What It Needs to Run
Included: the transmitter, and the 3-way valve manifold on “V” models.
Power: 13-30 VDC (2-wire), provided on site.
Ships: under 1 lb for the transmitter alone (10.1 oz); more with the valve manifold.
Genuine Taco equipment, factory-new in original packaging — sold and supported by Watermain Supply, an independent industrial supplier. Watermain Supply is an Authorized Taco Distributor.
Taco Warranty
Covered by Taco’s limited warranty. The Taco documents for this product do not state the term; ask us and we will confirm the current Taco terms before you order.
Specifications
| Service |
Compatible gases and liquids |
| Accuracy |
±0.5% FS |
| Temperature limits |
0 to 200°F; compensated 0 to 175°F |
| Thermal effect |
0.02%/°F including zero and span |
| Power / output |
13-30 VDC (2-wire); 4-20 mA, or 0-5 / 0-10 VDC |
| Response time |
50 msec |
| Connections |
Process 1/4 in female NPT; electrical terminal block, 1/2 in female NPT conduit |
From the Taco submittal data sheets, catalog and instruction sheets.
Models & Ranges
Each row is one Taco part number. The “V” models come with a 3-way valve manifold assembly with bleed screw.
| Model |
Output signal |
Range (psid) |
Working pressure (psid) |
Over pressure (psid) |
3-way valve |
| DPS629-03 |
4-20 mA |
0-25 |
50 |
250 |
No |
| DPS629-13 |
0-5 VDC |
0-25 |
50 |
250 |
No |
| DPS629-23 |
0-10 VDC |
0-25 |
50 |
250 |
No |
| DPS629-23D |
0-10 VDC |
0-25 |
50 |
250 |
No |
| DPS629-25 |
0-10 VDC |
0-100 |
200 |
500 |
No |
| DPS629-25D |
0-10 VDC |
0-100 |
200 |
500 |
No |
| DPS629-03V |
4-20 mA |
0-25 |
50 |
250 |
Yes |
| DPS629-13V |
0-5 VDC |
0-25 |
50 |
250 |
Yes |
| DPS629-23V |
0-10 VDC |
0-25 |
50 |
250 |
Yes |
| DPS629-23DV |
0-10 VDC |
0-25 |
50 |
250 |
Yes |
| DPS629-25DV |
0-10 VDC |
0-100 |
200 |
500 |
Yes |
From the Taco DPS629 submittal 301-2120 and catalog 300-35.
Before You Buy — The Limits That Decide the Fit
| Range |
Pick 25 psid (50 psid working) or 100 psid (200 psid working) to suit the pump or device differential |
| Signal |
Match the output (4-20 mA, 0-5 or 0-10 VDC) to the drive or controller input |
| Loop |
0-1,300 ohm maximum for current output; 2,000 ohm minimum load for voltage outputs |
Installation Notes
- Use a suitable pipe joint compound on the connections and avoid excess sealant that could block the ports
- Plan the conduit path from the transmitter to the control box
- The transmitter is not position sensitive
- Bleed air from the lines at start-up; the V models have a bleed screw on the valve manifold
From the Taco DPS629 submittal 301-2120 and Taco transmitter instruction sheets 302-065 and 302-066.
Applications
Pump differential pressure for variable speed pump control, and differential pressure across flow elements, heat exchangers, coils and filters.
Materials of Construction
| Part |
Standard |
| Wetted parts (no valve) |
316, 316L stainless steel |
| Added with 3-way valve |
Buna-N, silicone grease, PTFE, brass 360, copper, reinforced acetal copolymer |