Menu
Product variant with selected options does not exist!
files/Zoeller_61-HD-Series-Horizontal-Discharge_5667165f-7d45-476a-bdf2-15f562a79f2a.jpg
08:58 PM
The Zoeller Model 6121 is the 1.5 BHP member of the 61 HD Series, Zoeller Engineered Products’ 1750 RPM submersible solids handling pumps for municipal, commercial and industrial lift stations. The ductile iron semi-open impeller (5-3/8 in standard on 3-phase) passes 2-1/2 in spherical solids, with 3 in solids and a ductile iron vortex impeller available; discharge is a 3 in NPT vertical, 3 in horizontal flange or 4 in horizontal flange.
Every build in this listing is a configured Zoeller part number: voltage, discharge, cord length, seal materials, impeller type and trim, sensors and explosion proof construction are fixed by the part number, so what you order is what Zoeller builds and ships.
Included: the Zoeller pump built to the part number selected, with the cord length and options in that build.
Needs to run: a control panel matched to the pump voltage, phase and full load amps; three phase builds and builds with thermal or moisture sensors need panel circuits for those sensors. Zoeller Pivot panels and our team can match one to the pump.
| Model | 6121, 1.5 BHP, service factor 1.2 |
| Speed | 1750 RPM |
| Standard Impeller | Ductile iron semi-open, 5-3/8 in (3-phase standard); ductile iron vortex optional; trims to a design point on request |
| Solids | 2-1/2 in spherical standard; 3 in optional |
| Discharge | 3 in NPT vertical, 3 in horizontal flange or 4 in horizontal flange (ANSI B16.1) |
| Power Cord | 25 ft standard, #12-4 SOOW (#8-4 above 20 FLA) |
| Pump Weight | 245 lb |
| NEC Locked Rotor Code / Max kW | J / 1.9 kW |
| Full Load Amps | 230V 1Ph 8.9 · 200V 3Ph 5.9 · 230V 3Ph 5.1 · 460V 3Ph 2.6 · 575V 3Ph -- |
| Motor Options | Standard submersible; inverter duty (30-60 Hz, VPWM); dry pit and high temperature on 1-3 BHP (factory) |
From Zoeller Engineered Products Tech Data ZM1750 and Zoeller price data.
Find your total dynamic head (vertical lift plus pipe friction) and read across to the flow you need. Each row is a standard impeller; the build you select may carry a trimmed impeller sized to a design point.
Total head in feet at each flow
| Model | 0 GPM (Shut-off) | 40 GPM | 100 GPM | 150 GPM | 200 GPM |
|---|---|---|---|---|---|
| 6121 · semi-open, 5-3/8 in | 29 | 26 | 21 | 18 | 14 |
| 6121 · vortex impeller | 20 | 16 | 11 | 8 | 5 |
Read from Zoeller’s vector performance curve (Zoeller Engineered Tech Data ZM1750, 3-phase standard impellers (5-3/8 in semi-open; vortex)) and rounded down to the whole foot. Curve ends: 6121 at 327 GPM; 6121 · vortex impeller at 202 GPM. Trimmed impellers and the full curves are on the curve images and the Data Sheet tab; a trimmed build delivers less head than the standard impeller shown.
Pick the voltage, then the build: each build names the cord length, discharge, seals, sensors and impeller trim that Zoeller assembles for that part number.
| Voltage and Phase | Match the site supply exactly; three phase pumps need a three phase panel and starter. |
| Duty Point | Check the flow and total dynamic head against the performance curve (images and Data Sheet tab). Trimmed impeller builds are cut to a specific duty point. |
| Sensors | Thermal and moisture sensors only protect the pump when the control panel has circuits wired for them. |
| Explosion Proof | Explosion proof builds are for classified hazardous locations; confirm the area classification with the engineer of record. |
| Lead Time | Made to order: 4-6 weeks after receipt of order. Plan the install date around it. |
Product videos are being added to this listing. For a walkthrough in the meantime, email sales@watermainsupply.com.
Sign up for our newsletter and be the first to know about coupons and special promotions.
© 2026, Watermainsupply