The Smith-Blair Style 921 Top Bolt flanged coupling adapter (FCA) is a wide range plain end x flange adapter in fabricated steel: one part seals a wide range of pipe ODs within a nominal size, up to 1.31 in, to connect plain-end pipe to flanged fittings, meters, valves and other flanged equipment, 2 to 12 in. The 3-12 in flanges carry AWWA C207 Class D (ANSI 150 lb) drilling; the 2 in is a standard meter coupling flange.
The coupling end tightens with a single top bolt and stabs on with no disassembly. A removable, bi-directional channeled inner gasket covers the lower part of the range and comes out for pipe in the upper range, and the two-piece coupling flange can be taken apart on site to replace a gasket. Choose the nominal size; each size covers the full OD range in the table below.
Application: connecting steel, ductile iron, PVC, copper, AC and HDPE plain-end pipe to flanged fittings, meters and valves, 2 to 12 in.
Key Features
Included: the assembled adapter, with sleeve, flange, two-piece coupling flange, stainless armor, inner and outer gaskets, and the 304 stainless top bolt with nut and washers, ready to stab onto the pipe.
Pipe stiffeners on HDPE and thin-wall PVC, ordered separately. Smith-Blair requires them on those pipes; ask us to quote them with the adapter.
Smith-Blair warrants its products to be free of defects in materials and workmanship for one year from the date of shipment by Smith-Blair. Dated proof of purchase, such as a bill of sale, is required to establish eligibility. Smith-Blair will repair or, at its option, replace a defective product; the product is returned to the factory or warehouse Smith-Blair designates.
175 PSI on every size, 2 to 12 in. For a particular installation the allowable pressure also depends on pipe type and condition, service conditions and installation workmanship.
| Sleeve | Carbon steel per ASTM A283C, A285A or A36 |
| Flange | Carbon steel; AWWA C207 Class D, ANSI 150 lb drilling (3-12 in); standard meter coupling flange meeting ANSI B16.5 (2 in) |
| Coupling flange (ring) | Carbon steel per ASTM A283C, A285A or A36; split two-piece design with integral bolt-head pocket for one-wrench installation |
| Armor | Hardened Type 304 stainless steel, corrugated to cut friction against the gasket |
| Gasket | Nitrile (Buna-N) per ASTM D2000, NSF/ANSI 61 and 372; bi-directional removable inner gasket; resists water, oil, acids, alkalies and most (aliphatic) hydrocarbons; -20°F to +180°F |
| Bolt | Type 304 stainless steel, Flexi-Coat epoxy coated, 9/16-12 UNC swivel head with swivel washer |
| Nut | Heavy hex Type 304 stainless steel, fluoropolymer finish to prevent galling |
| Connector bolts | Type 304 stainless steel, 1/2-13 UNC countersunk Allen head |
| Washers | Type 304 stainless steel over a Nylon 6/6 washer for better torque transfer |
| Finish | Flexi-Coat fusion-bonded epoxy, 12-15 mils, applied to AWWA C213 methods |
Materials subject to change by the manufacturer.
Carbon steel, stainless steel, ductile iron, asbestos cement, PVC, copper tube and HDPE pipe. HDPE and thin-wall PVC take pipe stiffeners, which Smith-Blair requires on those pipes.
| Pipe size and OD |
|---|
| 2 in - 2.13-2.95 in OD |
| 3 in - 3.10-4.20 in OD |
| 4 in - 4.46-5.60 in OD |
| 6 in - 6.56-7.60 in OD |
| 8 in - 8.54-9.85 in OD |
| 10 in - 10.64-11.83 in OD |
| 12 in - 12.62-13.67 in OD |
Choose the size in the first option; the part number shows in the last option.
| Size | Overall range | Lower range | Upper range | Flange dia. | Laying length |
|---|---|---|---|---|---|
| 2 in | 2.13-2.95 in | 2.13-2.60 in | 2.50-2.95 in | 6.00 in | 6.81 in |
| 3 in | 3.10-4.20 in | 3.10-3.56 in | 3.70-4.20 in | 7.50 in | 5.38 in |
| 4 in | 4.46-5.60 in | 4.46-5.05 in | 5.00-5.60 in | 9.00 in | 5.50 in |
| 6 in | 6.56-7.60 in | 6.56-7.05 in | 7.00-7.60 in | 11.00 in | 6.56 in |
| 8 in | 8.54-9.85 in | 8.54-9.15 in | 9.15-9.85 in | 13.50 in | 6.56 in |
| 10 in | 10.64-11.83 in | 10.64-11.18 in | 11.13-11.83 in | 16.00 in | 6.56 in |
| 12 in | 12.62-13.67 in | 12.62-13.06 in | 13.10-13.67 in | 19.00 in | 6.69 in |
Lower range with the inner gasket in place; upper range with it removed. Minimum pipe insertion 2.88 in (2 in), 3.38 in (3 in) and 3.50 in (4-12 in).
From the Smith-Blair Style 921 Datasheet and 921 Specification (Rev 7/1/16), in the Data Sheet tab.