The Zoeller Model 165 Effluent Pump is a 1 HP effluent pump with a 1-1/2 in NPT discharge that passes 3/4 in solids. Printed performance runs from 61 GPM at 5 ft of total head to shut-off at 86.5 ft. It is listed here in 19 builds: 230V 1Ph · 230V or 460V 3Ph, with 20 to 50 ft cords.
The Model 165 high head effluent pump is engineered for performance in demanding residential and commercial wastewater environments, including onsite septic systems, pressure dose networks, and enhanced flow STEP applications. Its durable cast iron construction and corrosion resistant components ensure long lasting operation. Powered by a 1 HP oil-filled permanent split capacitor or 3 phase motor, offering excellent thermal dissipation during extended duration pumping cycles.
Which switch fits your pit? Tethered Float builds use Zoeller’s variable level piggyback float, which swings on its cord and lets you set a wider pumping range. Vertical Float builds carry Zoeller’s snap-action float switch on the pump, with fixed on and off levels, and suit narrow pits. No Switch builds are Zoeller’s nonautomatic models: they run from a separate piggyback float or a control panel.
Included: the pump with its power cord; Tethered Float and Vertical Float builds ship with that switch.
Float switch or control panel required, ordered separately, on No Switch builds. Zoeller’s nonautomatic models run from an external float switch or a control panel: see the Zoeller Piggyback Pump Switch and the Zoeller Pivot Control Panel.
Motor starter required, ordered separately, on three-phase builds: they run from a control panel with a magnetic starter and overload protection, such as the Zoeller Pivot Pro Control Panel.
Basin, check valve and discharge pipe: sized to the installation and ordered separately.
Zoeller lists a 1-year limited warranty on this product. The start date and conditions are in Zoeller’s published warranty statement.
| Horsepower | 1 HP |
| Voltage | 230V 1Ph · 230V or 460V 3Ph |
| Operation | Automatic, Nonautomatic |
| Switch | Snap-Action, Piggyback, None |
| Amps | 3.7 - 10.2 |
| RPM | 3450 |
| Discharge | 1-1/2 in NPT |
| Solids Handling | 3/4 in (19 mm) spherical solids |
| Impeller Material | Cast Iron |
| Impeller Type | Vortex |
| Cord Length | 20, 25, 35, 50 ft |
| Boxed Size | 21-1/4 H x 11-3/4 W x 14-3/4 L in |
| Shipping Weight | 82-91 lb |
From Zoeller’s published product specifications. Shipping weight is the boxed weight Zoeller publishes.
Find your total dynamic head (vertical lift plus pipe friction) in the left column and read the flow beside it.
Flow in GPM by total dynamic head
| Total head | Model 165 |
|---|---|
| 5 ft | 61 |
| 10 ft | 60.5 |
| 15 ft | 60.3 |
| 20 ft | 60 |
| 25 ft | 59 |
| 30 ft | 58 |
| 40 ft | 55 |
| Shut-off head | 86.5 ft |
Printed points from Zoeller Technical Data, 160 (4161, 4163) Series, FM2785: 60 Hz, verbatim. A dash means the pump does not reach that head. Shut-off head is where flow stops; pick a pump whose shut-off sits well above your total head. The full curve is in the image gallery and on the Data Sheet tab.
| Liquid and solids | Passes 3/4 in solids. |
| Lift | Flow stops at 86.5 ft of total head. Size on the flow at your own head, not on the maximum. |
| Switch | Tethered Float; Vertical Float; No Switch. No Switch builds need a float or panel. |
| Power | 230V 1Ph · 230V or 460V 3Ph, 60 Hz. Match the build to the supply at the basin. |
| Discharge | 1-1/2 in NPT |