A.Y. McDonald · Booster Pump
DuraMAC Variable Speed Duplex
Two A.Y. McDonald VS Booster pumps on one manifold and skid with a 6-gallon in-line pressure tank: double the flow at the same pressure, and a second pump in reserve.
78-79 PSI Max Boost · 40-70 GPM Max Flow
50 PSI Boost at 20 GPM (1 HP) or 40 GPM (2 HP)
25 PSI Boost at 36 GPM (1 HP) or 66 GPM (2 HP)
25-65 PSI Setting
2 x 1 HP or 2 x 2 HP
120V or 230V 1Ph
Built-In VFD on Each Pump
6 Gal In-Line Tank on the Manifold
Self-Priming
120 PSI Max Working Pressure
NSF 61 Compliant Pumps
76-89 lb System
Overview
The DuraMAC Variable Speed Duplex is a packaged booster built by Watermain Supply on two A.Y. McDonald Variable Speed Booster pumps, the 1 HP 17080V022C-1 for homes and the 2 HP 17080V037C-2 for light commercial work. Both pumps sit on one suction and discharge manifold on a common skid, with a 6-gallon A.Y. McDonald in-line diaphragm tank mounted on the manifold.
Each pump carries its own variable frequency drive, pressure sensor, built-in tank and suction check valve, so each holds the set point on its own. Running together they deliver twice the flow of one pump at the same pressure; if one pump is out for service, the other keeps the building in water.
- Two VS Booster pumps, each with its own drive and keypad
- Double the flow: up to 40 GPM (1 HP pair) or 70 GPM (2 HP pair)
- A pump in reserve: either pump carries the load alone
- 6-gallon in-line diaphragm tank on the manifold to cut cycling
- Self-priming, stainless pump casing and impellers
What Ships and What It Needs to Run
Included: two A.Y. McDonald VS Booster pumps (each with built-in drive, pressure tank, discharge pressure sensor and suction check valve), the suction and discharge manifold and skid, and a 6-gallon A.Y. McDonald 16006-V3M in-line diaphragm tank mounted on the manifold.
Power, one circuit per pump. Two 120V circuits on the 1 HP duplex (5.6 A each), or two 230V circuits on the 2 HP duplex (5.9 A each).
Supply and discharge piping, unions and isolation valves: sized to your installation and ordered separately.
Genuine A.Y. McDonald pumps, factory-new in original packaging — sold and supported by Watermain Supply, an independent industrial supplier. Watermain Supply is an Authorized Stocking A.Y. McDonald and Baker Water Systems Distributor.
3-Year A.Y. McDonald Pump Warranty
Each VS Booster pump is covered for 3 years from the date of installation under A.Y. McDonald’s published limited warranty terms. The diaphragm tank carries A.Y. McDonald’s own tank warranty.
Two Pumps, One Building
Two pumps hold more pressure at the flow the building draws. With both running, each carries half the water and sits higher on its own curve: the 2 HP pair adds 50 psi at 40 GPM, where one 2 HP pump adds 50 psi at 20 GPM. Pressure at zero flow stays at the single-pump figure, because it is set by the pump model.
The two pumps run as a set in their booster-set mode (parameter GP01 = 1 on each pump). Both keep the same stop and restart pressures, and each adds a random 0 to 5 second delay when it starts and stops, so the pumps take turns at light demand and both run at the peak.
Specifications
| Pumps |
2 x A.Y. McDonald VS Booster: 17080V022C-1 (1 HP) or 17080V037C-2 (2 HP) |
| Set point |
25 to 65 psi, programmed on each pump’s keypad |
| Maximum working pressure |
120 psi, the pump casing rating, not the boost |
| Priming |
Self-priming, check valve on each pump’s suction |
| Pressure tank |
Built into each pump body, plus a 6-gallon A.Y. McDonald 16006-V3M in-line tank on the manifold |
| Power |
1 HP: 120V 1Ph, 5.6 A per pump. 2 HP: 230V 1Ph, 5.9 A per pump |
| Liquid temperature |
32 °F to 90 °F; ambient up to 104 °F |
| Motor |
2-pole induction, insulation class F, UL listed |
| Certification |
Pumps in compliance with NSF 61 |
| Weight |
About 76 lb (1 HP) and 89 lb (2 HP) as a system, estimated |
Models & Performance — Will It Do What You Need?
Pressure added in PSI by both pumps running at full speed, at system flow. Find your model and read across; the first column is the most it can add.
| Model |
0 GPM (Shut-off) |
20 GPM |
40 GPM |
60 GPM |
70 GPM (Max) |
| 2 x 17080V022C-1 · 1 HP |
79 |
50 |
22 |
— |
— |
| 2 x 17080V037C-2 · 2 HP |
78 |
65 |
49 |
32 |
22 |
| Model |
HP |
Voltage |
Amps |
Best operating range |
| 2 x 17080V022C-1 |
2 x 1 HP |
120V 1Ph |
5.6 A per pump |
12 to 36 GPM |
| 2 x 17080V037C-2 |
2 x 2 HP |
230V 1Ph |
5.9 A per pump |
20 to 68 GPM |
Drawing from a tank or cistern — nothing arrives with pressure, so what the pumps add is what you get: set to 50 psi, the 1 HP pair holds it to about 20 GPM and the 2 HP pair to about 40 GPM.
Fed by a city main — the pumps add on top of what arrives, but the drives will not hold more than 65 psi in total. On a 40 psi main set to 60 psi they only have to add 20 psi, and they deliver well beyond their tank-fed flow. Incoming pressure turns into extra flow at the same set point.
Derived from A.Y. McDonald’s published single-pump curves in the Baker Water Systems VS Booster brochure at 2 times the flow, pressure unchanged; the pump maker’s own two-pump table is built the same way. Readings are rounded down. Bold = the last point on that model’s curve, its max flow; — = beyond it. Zero flow is the shut-off point, a ceiling and not a working point. Feet of head = PSI × 2.31. The duplex curves are in the image gallery.
Before You Buy — The Limits That Decide the Fit
| Maximum settable pressure |
65 psi. The drives will not hold more than this in total, whatever arrives at the inlet. |
| Maximum working pressure |
120 psi. Incoming pressure plus pressure added must stay below this. |
| Suction |
Self-priming, check valve on each pump’s suction. |
| Power |
One circuit per pump: 120V 1Ph on the 1 HP, 230V 1Ph on the 2 HP. Confirm the service before ordering. |
| Pump control |
Each pump runs on its own drive and sensor. Booster-set mode (GP01 = 1) with the same stop and restart pressures on both pumps makes them work as a pair. |
| Water temperature |
32 °F to 90 °F liquid; ambient to 104 °F. A thermal expansion tank is still required at any storage water heater. |
Installation Notes
- Set GP01 = 1 on each pump and enter the same stop pressure (UP01) and restart pressure (UP02) on both.
- With the manifold tank in place, set AP05 = 1 on each pump if the pressure fluctuates.
- Charge the tank to 7 psi (0.5 bar) below the restart pressure, with the system drained.
- Fit isolation valves before and after the set, and keep the supply and discharge pipes no smaller than the manifold connections.
- Fit a relief valve on the discharge where incoming pressure plus the most the pumps can add would exceed 120 psi.
- Prime each pump through its fill plug before the first start.
From the manufacturer’s operating instructions for the two-pump booster set and the VS Booster pump manual.
Applications
Homes with high demand or two water heaters, small apartment buildings, offices, irrigation and any site that needs a pump in reserve.
Materials of Construction
| Pump casing |
Stainless steel AISI 304 |
| Pump shaft |
Stainless steel AISI 316 |
| Impeller |
Stainless steel AISI 304 |
| Built-in tank membrane |
Butyl |
| Mechanical seal |
Carbon / ceramic, EPDM and stainless steel 316 |
Pump components, per the Baker Water Systems VS Booster brochure.